Early Warning of Incipient Faults for Power Transformer Based on DGA Using a Two-Stage Feature Extraction Technique

2021 
Early warning for transformer faults is valuable for maintenance decision-making. However, limited work has been done in this area due to the difficulty of the model establishment. This paper proposes a two-stage feature extraction method for early warning of power transformer faults. By combining feature ranking and genetic programming (GP), a novel feature extraction process is presented. In the first stage, the data is labeled as normal and fault states and the feature extraction is evaluated on the data. Then, extracted key features and their growth rates are relabeled as normal and warning states. The feature extraction process is evaluated again on relabeled data. Obtained features and logic expression can be used for early warning. The proposed framework can implement an early warning with about 100 days in advance for transformer faults and is verified through 8 sequences of data. The comparisons with two recently reported methods show the superiority of the proposed method.