Indoor Climate and Indoor Air Quality in Residential Buildings

1993 
In buildings which were built within the last 15 to 20 years, or which have been retrofitted, and which do notfeature a mechanical ventilation system, air changes between 0.01 h−1 and 0.5 h−1 were measured while windows were closed. In the bedrooms of such buildings, when doors and windows were closed, CO2 concentrations of up to 4300 ppm were measured whereby the 1500 ppm limit was often exceeded. Simulation calculations and diverse measurements using different door positions with simultaneously closed windows have shown that with the door open more than 10 cm, and a minimal air exchange in the whole of an apartment of 0.1 h−1, a CO2 concentration of I500 ppm was not or was only insignifiantly exceeded even after 10 hours. Investigations in a dwelling fined with a mechanical ventilation system have shown that air quality and the indoor climate parameters were in an optimal range.